KYORITSU KEW 5410 RCD Tester


245,000.00

The latest KYORITSU KEW 5410 RCD Tester price in Pakistan is Rs. 245,000/- updated on June 22, 2026.

FEATURES:

  • Measurement of RCD trip time Conducting testing of rated residual non-operating currents at × 1/2 Range, measuring RCD trip time at × 1 and × 5 Ranges.
  • Measurement of trip out current Measuring trip out current by varying   current automatically.
  • Remote Test Enabling a user to hold the Test Leads with his both hands by locking the Test Button. Measurement will automatically start when the main voltage is detected.
  • Voltage Measurement Carrying out a constant measurement of voltage in the range
  • stand-by mode at each Range.
  • Auto-detection of Contact voltage detecting the voltage to earth of Earth electrodes or protective conductors during RCD test – when applying test currents – at measurement using EARTH in order to prevent electrical shocks caused by the damaged earth. Measurement will be ceased at AC50V or more.
  • Dust- and Water-proof dust- and Water-proof construction(designed to IEC 60529 IP54).
  • BacklightFacilitating working at dimly illuminated locations.
Documents:

KYORITSU KEW 5410 RCD Tester Data Sheet.pdf

Computers Specs

Rated Voltage100V±10%, 200V-10%~+32%, 400V±10%, 50/60Hz

Display Specification

Display1999 counts (3 1/2digits), Large LCD

Summary

Applicable standardsIEC 61010-1 Pollution degree2 CAT III 300V / CAT II 400V
IEC 61010-031
IEC 61557-1, 6
IEC 60529 (IP54)
Included Accessories7128A (Test leads)
7129A (Test lead with alligator clip)
8017 (Long pin) × 2
Cord case, 9121 (Shoulder strap), Instruction manual,
R6(AA) × 8
Operating temperature & humidity range0ºC – 40ºC, relative humidity 85% (no condensation)
Optional Accessories7100A (Precision measurement cord set)
Overload protectionEarth Resistance: 280V AC for 10 seconds
across 2 of the 3 terminals
Earth Voltage: 300V AC for 1 minute
Safety StandardIEC 61010-1 CAT III 300V Pollution Degree 2, IEC 61557
Storage temperature & humidity range-20ºC – 60ºC, relative humidity 85% (no condensation)
Accuracy(Measurement of RCD trip time – Measurement of trip out current)
(Trip Time)
(× 5) 1%rdg±3dgt, (x 1) 1%rdg±3dgt, (x 1/2) 1%rdg±3dgt, (AUTO RAMP mA) Test Current at each step -4%~+4%
(Trip Time)
(× 5) +2%~+8%dgt, (x 1) +2%~+8%dgt, (x 1/2) -8%~-2%dgt
(Voltage Measurement)
2%rdg±4dgt
Measuring rangeTesting time = 0ms~200ms
Testing time = 0ms~2000ms
Testing time = 0ms~2000ms
40% – 110% of lΔn (goes up by 5%) Testing time 300ms × 15steps
(Voltage Measurement)
80V~450V 50/60Hz
WeightApprox. 965g (including batteries)
Insulation Resistance50MΩ or more / 1000V (between electrical circuit and enclosure)
Range(x 5) (x 1) (x 1/2) (AUTO RAMP mA)
Test Current (approx.)15/30/50/100mA, 15/30/50/100/200/500mA, 15/30/50/100/200/500mA
Power SourceDC 12V / R6(AA)(1.5V) × 8

General Specification

Dimensions167(L)×186(W)×89(D)mm

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “KYORITSU KEW 5410 RCD Tester”

There are no reviews yet.

Select at least 2 products